LY2000 Series

LY2000 Series

Technical Parameters (Natural Gas):


Generator Set Model: LY2000AGL/M/H-T
Electrical Power:2000 kW
Fuel Consumption:4808 kW
Electrical Efficiency:42%
Thermal Efficiency: 46.5%
Total Efficiency: 88.5%
Frequency:50 / 60Hz

Dimensions(LxWxH): 7450 x 1700 x 2700 mm 1}


Note: Factors such as gas quality, air pressure, calorific value, operating environment, and personnel operation level will affect the final output of the unit.

1}For the transportation size of genset, the components set separately must be considered separately.


INQUIRY NOW

Introduction

文本文字

NOx ≤ 500 mg/Nm³  2}

Application Area

Unit

Natural Gas Application 50/60Hz

Associated Petroleum Gas Application   50/60Hz

Low-Concentration CBM Application   50/60Hz

Biogas Application 50/60Hz

Industrial Gas Application 50/60Hz

Biomass Gas Application 50/60Hz

Blast Furnace Gas Application 50/60Hz

Coal-to-Gas Application 50/60Hz

Genset Model

LY2000AGL/M/H-T

LY2000AGL/M/H-T1

LY2000AGL/M/H-WL

LY2000AGL/M/H-Z

LY2000AGL/M/H-M

LY2000AGL/M/H-S

LY2000AGL/M/H-G

LY2000AGL/M/H-M1

Electrical Power3} (±5%)

kW

2000

1500

1850

1900

1500

1400

1400

1500

Fuel Consumption

kW

4808

3896

4591

4390

3741

3684

3723

3896

Electrical Efficiency4}

%

42.0

38.5

40.3

41.0

40.1

38.0

37.6

38.5

Thermal Efficiency

%

46.5

48.5

47.9

46.3

47.6

48.2

48.7

47.9

Total Efficiency

%

88.5

87.0

88.2

87.3

87.7

86.2

86.3

86.4

Note: Factors such as gas quality, air pressure, calorific value, operating environment, and personnel operation level will affect the final output of the unit.
• Sewage Treatment Biogas (65%CH₄ / 35%CO₂)
• Biomass gas (60%CH₄ / 32%CO₂, the rest are N₂)
• Landfill gas (50%CH₄ / 27%CO₂, the rest are N₂)
• Industrial gas (75%CO, 6%H₂, 3%CH₄, 9%CO₂, the rest are N₂)
2}NOx emission: NOx ≤ 500 mg/Nm³, NOx/Nm³ (Content of dry exhaust gas in 5% O₂)
3}Refers to ISO8525-1, 50Hz Generator U=10kV, Cosphi=1.0, the minimum methane number of natural gas is MN70
4}Refers to ISO3046-1, 50Hz Generator U=10kV, Cosphi=1.0, the minimum methane number of natural gas is MN70